Effectiveness Performance Data
HRV2000i/e - POLYPROPYLENE AND ALUMINUM CORES
Model Number: PHE500-15.4H-15.3S-0.11
Model Number: AHE500-15.4H-15S-0.14
Type: Plate (Plate) Nominal Airflow: 530 (530) scfm
Pressure Drop: 0.86 (0.30) inches
Leakage Ratings
Pressure Purge Angle
Differential EATR OACF or Setting
Test 1: -5.00 (-3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 2: 0.00 (0.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 3: 5.00 (3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Thermal Effectiveness Ratings at 0" Pressure Differential
Sensible Latent Total
100% Airflow Heating Condition: 58% (52%) 0% (0%) 38% (34%)
75% Airflow Heating Condition: 63% (58%) 0% (0%) 42% (38%)
100% Airflow Cooling Condition: 49% (46%) 0% (0%) 19% (18%)
75% Airflow Cooling Condition: 55% (52%) 0% (0%) 21% (20%)
Net Sensible Net Latent Net Total
100% Airflow Heating Condition: 58% (52%) 0% (0%) 38% (34%)
75% Airflow Heating Condition: 63% (58%) 0% (0%) 42% (38%)
100% Airflow Cooling Condition: 49% (46%) 0% (0%) 19% (18%)
75% Airflow Cooling Condition: 55% (52%) 0% (0%) 21% (20%)
1000
10%
30%
50%
70%
Effectiveness
1450 1900 2350 2800
472 684 897
Airflow (L/s)
1109 1322
Airflow (cfm)
B
ased on equal amounts of outdoor air and return air.
Total Effectiveness (Cooling)
Sensible Effectiveness (Heating)
Latent Effectiveness (Heating)
Ratings outside the scope of the
A
HRI Energy Recovery Ventilation Certification Program.
n/a
Energy recovery component is certified by
AHRI to AHRI Standard 1060. Actual
performance in packaged equipment may vary.
HRV2000i/e - HM CORE
Model Number: EPE5000-15.3H-15S-0.1
Type: Plate Nominal Airflow: 530 scfm
Pressure Drop: 0.75 inches
Leakage Ratings
Pressure Purge Angle
Differential EATR OACF or Setting
Test 1: -0.50 inches 1.0% 1.00 N/A
Test 2: 0.00 inches 0.5% 1.01 N/A
Test 3: 0.50 inches 0.0% 1.01 N/A
Thermal Effectiveness Ratings at 0" Pressure Differential
Sensible Latent Total
100% Airflow Heating Condition: 54% 44% 51%
75% Airflow Heating Condition: 59% 49% 55%
100% Airflow Cooling Condition: 54% 30% 39%
75% Airflow Cooling Condition: 59% 37% 45%
Net Sensible Net Latent Net Total
100% Airflow Heating Condition: 54% 44% 51%
75% Airflow Heating Condition: 59% 49% 55%
100% Airflow Cooling Condition: 54% 30% 39%
75% Airflow Cooling Condition: 59% 37% 45%
1000
10%
30%
50%
70%
Effectiveness
1450 1900 2350 2800
472 684 897
Airflow (L/s)
1109 1322
Airflow (cfm)
Based on equal amounts of outdoor air and return air.
Total Effectiveness (Cooling)
Sensible Effectiveness (Heating)
Latent Effectiveness (Heating)
Ratings outside the scope of the
AHRI Energy Recovery Ventilation Certification Program.
Energy recovery component is certified by
AHRI to AHRI Standard 1060. Actual
performance in packaged equipment may vary.