Effectiveness Performance Data
HRV2000i/e - POLYPROPYLENE AND ALUMINUM CORES
Model Number: PHE500-15.4H-15.3S-0.11
Model Number: AHE500-15.4H-15S-0.14
Type: Plate (Plate) Nominal Airflow: 530 (530) scfm
Pressure Drop: 0.86 (0.30) inches
Leakage Ratings
Pressure Purge Angle
Differential EATR OACF or Setting
Test 1: -5.00 (-3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 2: 0.00 (0.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Test 3: 5.00 (3.00) inches 0% (0%) 1.00 (1.00) N/A (N/A)
Thermal Effectiveness Ratings at 0" Pressure Differential
Sensible Latent Total
100% Airflow Heating Condition: 58% (52%) 0% (0%) 38% (34%)
75% Airflow Heating Condition: 63% (58%) 0% (0%) 42% (38%)
100% Airflow Cooling Condition: 49% (46%) 0% (0%) 19% (18%)
75% Airflow Cooling Condition: 55% (52%) 0% (0%) 21% (20%)
Net Sensible Net Latent Net Total
100% Airflow Heating Condition: 58% (52%) 0% (0%) 38% (34%)
75% Airflow Heating Condition: 63% (58%) 0% (0%) 42% (38%)
100% Airflow Cooling Condition: 49% (46%) 0% (0%) 19% (18%)
75% Airflow Cooling Condition: 55% (52%) 0% (0%) 21% (20%)
1000
10%
30%
50%
70%
Effectiveness
1450 1900 2350 2800
472 684 897
Airflow (L/s)
1109 1322
Airflow (cfm)
B
ased on equal amounts of outdoor air and return air.
Total Effectiveness (Cooling)
Sensible Effectiveness (Heating)
Latent Effectiveness (Heating)
Ratings outside the scope of the
A
HRI Energy Recovery Ventilation Certification Program.
n/a
Energy recovery component is certified by
AHRI to AHRI Standard 1060. Actual
performance in packaged equipment may vary.