Blower Motor Specifications Unit Specifications
HRV600i, HRV700i, HRV1200i
HRV600i
HRV700i
HRV1200i
HP
1/4
1/6
1/3
MCA
9.5
6.6
14.3
MOP
12
9
20
Motor
Voltage
120/1/60
120/1/60
120/1/60
Unit
Voltage
120V
120V
120V
Unit
FLA
8.6
6.0
12.8
Motor
FLA
3.8
2.5
5.9
Page 20
Electrical Data
ODP MOTOR MEDIUM EFFICIENCY
MCA Calculation
1.25 x _____ FLA of larger HP motor or compressor = ________
1.25 x _____ Heater FLA = + ________
Sum of all other motors FLA = + ________
Wheel drive motor and standard controls FLA = + ________
Indirect gas heater FLA = + ________
Calculated Total MCA = ________
MOP Calculation
2.25 x _____ FLA of larger HP motor or compressor = ________
Electric heater FLA = + ________
Sum of all other motors FLA = + ________
Wheel drive motor and standard controls FLA = + ________
Indirect gas heater FLA = + ________
Calculated Total MOP = ________
Actual MOP = ________
(from Standard Overcurrent Protection Chart)
Finding the Actual MOP Value
From the calculated MOP value, select the next
smallest value of protection from the Standard
Overcurrent Protection chart below to get the Actual
MOP value (maximum value of overcurrent device).
Note: If this method leads to an Actual MOP value
being smaller than the Calculated Total MCA, then
a larger value must rather be selected, such that
the Actual MOP is at least equal to the Calculated
Total MCA.
3 40 250
4 45 300
5 50 350
6 60 400
7 70 450
8 80 500
9 90 600
10 100 650
12 110 700
15 125 750
20 150 800
25 175 850
30 200 900
35 225 1000
Standard Overcurrent Protection
NOTES: MOP - Maximum overcurrent protection
MCA - Minimum current ampacity
CAUTION
All electrical installations and wiring require correct wire gauge
sizing and protection according to local building codes.
WARNING
All units equipped with electric post-heaters require two point
power connections.
208/1/60 230/1/60 208/3/60 230/3/60 460/3/60 575/3/60
Voltage
208/1/60 230/1/60 208/3/60 230/3/60 460/3/60 575/3/60
VOLTAGE
HP
Controls Full Load Amperage (FLA)
Blower Motor Full Load Amperage (FLA) HRV2000i/e
4.5
5.4
6.8
10.2
14.0
17.8
1/2
3/4
1.0
1.5
2.0
3.0
4.0
6.0
7.0
10.2
14.0
17.0
1.8
2.7
3.4
5.0
6.4
10.6
2.2
2.7
3.4
5.0
6.0
10.6
1.1
1.4
1.7
2.5
3.0
4.8
0.9
1.1
1.4
2.0
2.4
3.4
0.48 0.43 0.48 0.43 0.22 0.17
NOTE: The blower motor FLA values shown above are for one motor only.